ZEYTOON WIRE & CABLE CO products

 
Fixed Installation Wires

Fixed Installation Wires

Applications

This type of wire is used in the internal wiring of electrical panels and distributors. The use of these wires in conduits and beneath plaster is permitted. Wires with stranded conductors (Group 2) can be used as electrical connections in underground ducts, machinery, control panels, and control equipment.

 

Structure

Conductor: Annealed copper, Group 1 (solid single core) or Group 2 (stranded) according to IEC Standard 60228 or ISIRI 3084.
Insulation: PVC blend of type C/PVC.
 

Standard

• IEC 60227 or ISIRI 607 with a nominal voltage of 750/450 volts for cross-sectional areas greater than 1 square millimeter. • IEC 60227 or ISIRI 607 with a nominal voltage of 500/300 volts for cross-sectional areas of 0.75, 1.0, and 5.0 square millimeters.

Nominal Conductor Area
(mm²)
Conductor Group Insulation Thickness
(mm)
Outer Diameter Range
(Lower - Upper)
(mm)
Max Resistance of Insulation at 70°C
(MΩ.km)
Max Conductor Resistance at 20°C
(Ω/km)
Approximate Weight
(Kg/km)
0.5 1 0.6 1.9 2.3 0.0150 36 8
0.75 1 0.6 2.1 2.5 0.0120 24.5 11
1 1 0.6 2.2 2.7 0.0110 18.1 14
1.5 1 0.7 2.6 3.2 0.0110 12.1 20
2.5 1 0.8 3.3 4.0 0.0090 7.41 31
2.5 2 0.8 3.3 4.0 0.0090 7.41 33
4 1 0.8 3.6 4.4 0.0085 4.61 46
4 2 0.8 3.8 4.6 0.0077 4.61 48
6 1 0.8 4.1 5.0 0.0070 3.08 66
6 2 0.8 4.3 5.2 0.0065 3.08 69
10 1 1.0 5.3 6.4 0.0070 1.83 105
10 2 1.0 5.7 6.8 0.0065 1.83 110
16 2 1.0 6.4 7.8 0.0050 1.15 169
25 2 1.2 8.1 9.7 0.0050 0.727 262
35 2 1.2 9.0 10.9 0.0043 0.524 354
50 2 1.4 10.6 12.8 0.0043 0.387 490
70 2 1.4 12.1 14.6 0.0035 0.268 678
95 2 1.6 14.1 17.1 0.0035 0.193 935
120 2 1.6 15.6 18.8 0.0032 0.153 1165
150 2 1.8 17.3 20.9 0.0032 0.124 1436
185 2 2.0 19.3 23.3 0.0032 0.0991 1795
240 2 2.2 22 26.6 0.0032 0.0754 2345